| DTC B1260, B1261, B1282, B1283, B1274, B1275, P0532, P0533 |
Climate control unit (+5 V power supply) system |
|---|---|
|
POSSIBLE CAUSE
|
• Open or short circuit in wiring harnesses between climate control unit and solar radiation sensor, air mix actuator, airflow mode actuator, or refrigerant pressure sensor.
|
Diagnostic Procedure
| STEP |
INSPECTION |
ACTION |
|
|---|---|---|---|
|
1
|
• Disconnect the climate control unit connector and the airflow mode actuator connector.
• Is there an open circuit in the wiring harness between climate control unit terminal 1J and airflow mode actuator terminal B?
|
Yes
|
Repair the wiring harness.
|
|
No
|
Go to the next step.
|
||
|
2
|
• Is there a short circuit to ground in the wiring harness between climate control unit terminal 1J and airflow mode actuator terminal B?
|
Yes
|
Repair the wiring harness.
|
|
No
|
Go to the next step.
|
||
|
3
|
• Is there a short circuit to ground in the wiring harness between climate control unit terminal 1J and air mix actuator terminal A?
|
Yes
|
Repair the wiring harness.
|
|
No
|
Go to the next step.
|
||
|
4
|
• Is there a short circuit to ground in the wiring harness between climate control unit terminal 1J and solar radiation sensor terminal A?
|
Yes
|
Repair the wiring harness.
|
|
No
|
Go to the next step.
|
||
|
5
|
• Is there a short circuit to ground in the wiring harness between climate control unit terminal 1J and refrigerant pressure sensor terminal A?
|
Yes
|
Repair the wiring harness.
|
|
No
|
The system is normal at present. (Clear the malfunction from the memory.)
|
||
|
|||