NO.2 AMOUNT OF AIR BLOWN FROM VENTS DOES NOT CHANGE [MANUAL AIR CONDITIONER]SM2445628
NO.2 AMOUNT OF AIR BLOWN FROM VENTS DOES NOT CHANGE [MANUAL AIR CONDITIONER]

id0703c2800500

2
Amount of air blown from vents does not change.
DESCRIPTION
• Malfunction in blower system
POSSIBLE CAUSE
• Blower relay, blower motor, resistor, airflow volume control dial malfunction
• A/C unit malfunction
• Clogged in A/C unit passage

Diagnostic procedure

STEP

INSPECTION

ACTION

1
INSPECT BLOWER SYSTEM
• Inspect the following systems and electrical parts.
― Blower relay
― Blower motor
― Resistor
― Airflow volume control dial
― Related wiring harnesses
• Are they normal?
Yes
Go to the next step.
No
Repair or replace the malfunctioning part, then go to Step 5.
2
INSPECT TO SEE WHETHER MALFUNCTION IS IN A/C UNIT OR ELSEWHERE
• Turn the ignition switch to the ON position.
• Turn the airflow volume control dial on.
• Recirculate air inside the vehicle.
• Does the blower motor rotate smoothly?
Yes
Go to Step 4.
No
Go to the next step.
3
INSPECT A/C UNIT
• Inspect blower motor.
― Is the fan free of interference from the A/C unit case?
― Is the fan free of foreign material and obstructions?
• Is the fan normal?
Yes
Go to the next step.
No
Remove obstruction, repair or replace the fan and A/C unit case, then go to Step 5.
4
INSPECT A/C UNIT INTAKE VENT
• Is the A/C unit intake vent clogged?
Yes
Remove obstruction, then go to the next step.
No
Inspect if there are any obstructions in the A/C unit passage, then go to the next step.
5
VERIFY THAT MALFUNCTION SYMPTOM OCCURS AFTER REPAIR
• Does air blow out?
Yes
Troubleshooting completed.
Explain repairs to customer.
No
Recheck malfunction symptoms, then repeat from Step 1 if the malfunction recurs.