ON-BOARD DIAGNOSTIC FUNCTION
id070200100300
Malfunction detection function
Fail-safe function
Fail-safe Function Table
Part where malfunction is determined |
Malfunction determined when IG SW at ON |
Malfunction already exists when IG SW turned to ON |
---|---|---|
Cabin temperature sensor
|
Cabin temperature sensor input value is fixed at 25 °C {77 °F}.
|
←
|
Ambient temperature sensor
|
Ambient temperature sensor input value is fixed at 15 °C {59 °F}.
|
←
|
Evaporator temperature sensor
|
Evaporator temperature sensor input value is fixed at 0 °C {32 °F}.
|
←
|
Solar radiation sensor
|
Solar radiation sensor value is fixed at 0 W/m2.
|
←
|
Air mix actuator
(potentiometer)
|
Air mix actuator drive signal is stopped right when the malfunction is determined.
|
• The actuators are driven as follows according to the voltage detected at the potentiometer circuit.
• If the potentiometer circuit voltage is between 0.1 to 4.9 V within 2 s from when the ignition switch is turned to the ON position, the actuator switches to the normal operation.
• If the actuator does not switch to the normal operation within 2 s, the actuator drive signal is stopped.
|
Airflow mode actuator
(potentiometer)
|
Airflow mode actuator drive signal is stopped right when the malfunction is determined.
|
• The actuators are driven as follows according to the voltage detected at the potentiometer circuit.
• If the potentiometer circuit voltage is between 0.1 to 4.9 V within 2 s from when the ignition switch is turned to the ON position, the actuator switches to the normal operation.
• If the actuator does not switch to the normal operation within 2 s, the actuator drive signal is stopped.
|
Air mix actuator
(motor lock)
|
Air mix actuator drive signal is stopped right when the malfunction is determined.
|
After the IG SW is at ON, the air mix actuator drive signal is again output normally.
|
Airflow mode actuator
(motor lock)
|
Airflow mode actuator drive signal is stopped right when the malfunction is determined.
|
After the IG SW is at ON, the airflow mode actuator drive signal is again output normally.
|
Serial communication between the front climate control unit and the rear climate control unit
|
Preserves the normal data last received until malfunction is repaired.
|
Disables the communication data (turns off all rear climate control unit switches)
|
Serial communication between the front climate control unit and the instrument cluster
|
Inputs the normal data last received until communication is completed. After completing communication, inputs the engine coolant temperature 80 °C {176 °F}and the vehicle speed 0 km/h {0 mph}, and controls the full-auto air conditioner.
|
Does not turn on the A/C until communication is completed. After communication is completed, inputs the engine coolant temperature 80 °C {176 °F} and the vehicle speed 0 km/h {0 mph}, and controls the full-auto air conditioner.
|
The front climate control unit receives invalid engine coolant temperature signal data from the instrument cluster
|
Inputs the correct data last received until reception is completed. After reception is completed, inputs the engine coolant temperature 80 °C {176 °F}, and controls the full-auto air conditioner.
|
Does not turn on the A/C until reception is completed. After reception is completed, inputs the engine coolant temperature 80 °C {176 °F}, and controls the full-auto air conditioner.
|
Memory Function
Display Function
Present Malfunction Display Mode
DTC Table
No. |
Output pattern |
Malfunction location |
Detected condition |
Memory function |
---|---|---|---|---|
02
|
![]() |
Solar radiation sensor (present malfunction)
|
Solar radiation sensor (RH) circuit short
|
—
|
04
|
![]() |
Solar radiation sensor (LH) circuit short
|
—
|
|
06
|
![]() |
Cabin temperature sensor (present malfunction)
|
Cabin temperature sensor circuit open/short circuit
|
—
|
10
|
![]() |
Front evaporator temperature sensor (present malfunction)
|
Front evaporator temperature sensor circuit open/short circuit
|
—
|
12
|
![]() |
Ambient temperature sensor (present malfunction)
|
Ambient temperature sensor circuit open/short circuit
|
—
|
18
|
![]() |
Driver-side front air mix actuator (potentiometer) (present malfunction)*1
Passenger-side front air mix actuator (potentiometer) (present malfunction)*2
|
Driver-side front air mix actuator (potentiometer) circuit open/short circuit*1
Passenger-side front air mix actuator (potentiometer) circuit open/short circuit*2
|
—
|
21
|
![]() |
Front airflow mode actuator (potentiometer) (present malfunction)
|
Front airflow mode actuator (potentiometer) circuit open/short circuit
|
—
|
37
|
![]() |
Passenger-side front air mix actuator (potentiometer) (present malfunction)*1
Driver-side front air mix actuator (potentiometer) (present malfunction)*2
|
Passenger- side front air mix actuator (potentiometer) circuit open/short circuit*1
Driver-side front air mix actuator (potentiometer) circuit open/short circuit*2
|
—
|
69
|
![]() |
Rear climate control unit communication system (present malfunction)
|
Between front climate control unit and rear climate control unit communication circuit open/short circuit
|
—
|
76
|
![]() |
Rear air mix actuator (potentiometer) (present malfunction)
|
Rear air mix actuator (potentiometer) circuit open/short circuit
|
—
|
78
|
![]() |
Rear evaporator temperature sensor (present malfunction)
|
Rear evaporator temperature sensor circuit open/short circuit
|
—
|
85
|
![]() |
Rear airflow mode actuator (potentiometer) (present malfunction)
|
Rear airflow mode actuator (potentiometer) circuit open/short circuit
|
—
|
Past Malfunction Display Mode
DTC Table
No. |
Output pattern |
Malfunction location |
Detected condition |
Memory function |
---|---|---|---|---|
07
|
![]() |
Cabin temperature sensor (past malfunction)
|
When an open/short has occurred in the cabin temperature sensor circuit 1 time or more in the past
|
X
|
11
|
![]() |
Front evaporator temperature sensor (past malfunction)
|
When an open/short has occurred in the front evaporator temperature sensor circuit 1 time or more in the past
|
X
|
13
|
![]() |
Ambient temperature sensor (past malfunction)
|
When an open/short has occurred in the ambient temperature sensor circuit 1 time or more in the past
|
X
|
19
|
![]() |
Driver-side front air mix actuator (potentiometer) (past malfunction)*1
Passenger-side front air mix actuator (potentiometer) (past malfunction)*2
|
When an open/short has occurred in the driver-side front air mix actuator (potentiometer) circuit 1 time or more in the past*1
When an open/short has occurred in the passenger-side front air mix actuator (potentiometer) circuit 1 time or more in the past*2
|
X
|
22
|
![]() |
Front airflow mode actuator (potentiometer) (past malfunction)
|
When an open/short has occurred in the front airflow mode actuator (potentiometer) circuit 1 time or more in the past
|
X
|
38
|
![]() |
Passenger-side front air mix actuator (potentiometer) (past malfunction)*1
Driver-side front air mix actuator (potentiometer) (past malfunction)*2
|
When an open/short has occurred in the passenger-side front air mix actuator (potentiometer) circuit 1 time or more in the past*1
When an open/short has occurred in the driver-side front air mix actuator (potentiometer) circuit 1 time or more in the past*2
|
X
|
58
|
![]() |
Driver-side front air mix actuator (motor lock) (past malfunction)*1
Passenger-side front air mix actuator (motor lock) (past malfunction)*2
|
When motor lock has occurred in the driver-side front air mix actuator circuit 1 time or more in the past*1
When motor lock has occurred in the passenger-side front air mix actuator circuit 1 time or more in the past*2
|
X
|
59
|
![]() |
Front airflow mode actuator (motor lock) (past malfunction)
|
When motor lock has occurred in the front airflow mode actuator circuit 1 time or more in the past
|
X
|
61
|
![]() |
Passenger-side front air mix actuator (motor lock) (past malfunction)*1
Driver-side front air mix actuator (motor lock) (past malfunction)*2
|
When motor lock has occurred in the passenger-side front air mix actuator circuit 1 time or more in the past*1
When motor lock has occurred in the driver-side front air mix actuator circuit 1 time or more in the past*2
|
X
|
68
|
![]() |
Rear climate control unit communication system (past malfunction)
|
When an open/short has occured in the between front climate control unit and rear climate control unit communication circuit 1 time or more in the past
|
X
|
77
|
![]() |
Rear air mix actuator (potentiometer) (past malfunction)
|
When an open/short has occurred in the rear air mix actuator (potentiometer) circuit 1 time or more in the past
|
X
|
79
|
![]() |
Rear evaporator temperature sensor (past malfunction)
|
When an open/short has occurred in the rear evaporator temperature sensor circuit 1 time or more in the past
|
X
|
86
|
![]() |
Rear airflow mode actuator (potentiometer) (past malfunction)
|
When an open/short has occurred in the rear airflow mode actuator (potentiometer) circuit 1 time or more in the past
|
X
|
95
|
![]() |
Rear air mix actuator (motor lock) (past malfunction)
|
When motor lock has occurred in the rear air mix actuator circuit 1 time or more in the past
|
X
|
96
|
![]() |
Rear airflow mode actuator (motor lock) (past malfunction)
|
When motor lock has occurred in the rear airflow mode actuator circuit 1 time or more in the past
|
X
|
A/C Operation Check Mode
Step |
Target part |
Operation condition |
Monitor display* |
---|---|---|---|
1
|
Front climate control unit
|
![]() |
Entire illumination of climate control display
|
Information display
|
![]() |
||
2
|
Blower motor
|
![]() |
01
|
3
|
Air mix door
|
![]() |
20.0 (0%)
20.5 (50%)
21.0 (100%)
20.5 (50%)
|
4
|
Airflow mode door
|
![]() |
03
|
5
|
Air intake door
A/C compressor
|
FRESH Û REC
ON Û OFF
|
04
|