NO.3 AIR INTAKE MODE FROM FRONT VENT DOES NOT CHANGE


id070300801700

3
Air intake mode from front vent does not change.
DESCRIPTION
•  Malfunction in A/C unit and/or front climate control unit air intake mode switching system
•  Air intake mode does not change when switching REC/FRESH mode.
POSSIBLE CAUSE
•  Air intake actuator malfunction
•  Air intake door malfunction

•  When performing an asterisked (*) troubleshooting inspection, shake the wiring harness and connectors while doing the inspection to discover whether poor contact points are the cause of any intermittent malfunctions. If there is a problem, inspect to make sure connectors, terminals and wiring harness are connected correctly and undamaged.

Diagnostic procedure

STEP

INSPECTION

ACTION

1
INSPECT AIR INTAKE ACTUATOR
•  Is the air intake actuator normal?
Yes
Go to the next step.
No
Replace the air intake actuator, then go to Step 9.
2*
INSPECT TO SEE WHETHER MALFUNCTION (OPEN OR SHORT CIRCUIT) IS IN AIR INTAKE ACTUATOR, WIRING HARNESS (BETWEEN CLIMATE CONTROL UNIT AND AIR INTAKE ACTUATOR) OR ELSEWHERE
•  Turn the ignition switch to the ON position.
•  Measure the voltages at the following climate control unit terminals.
R.H.D.
―  Terminal 1K (24-pin, RECIRCULATE motor drive signal)
―  Terminal 1M (24-pin, FRESH motor drive signal)
L.H.D.
―  Terminal 1M (24-pin, RECIRCULATE motor drive signal)
―  Terminal 1K (24-pin, FRESH motor drive signal)
•  Are voltages normal?
Yes
Go to the next step.
No
Go to Step 4.
3*
INSPECT TO SEE WHETHER MALFUNCTION (OPEN OR SHORT CIRCUIT) IS IN AIR INTAKE ACTUATOR OR WIRING HARNESS (BETWEEN CLIMATE CONTROL UNIT AND AIR INTAKE ACTUATOR)
•  Measure the voltages at the following air intake actuator terminals.
R.H.D.
―  Terminal A (RECIRCULATE motor drive signal)
―  Terminal C (FRESH motor drive signal)
L.H.D.
―  Terminal C (RECIRCULATE motor drive signal)
―  Terminal A (FRESH motor drive signal)
•  Are voltages as shown below?
R.H.D.
―  Terminal C: approx. 10 V during FRESH and approx. 0.5 V during RECIRCULATE
―  Terminal A: approx. 0.5 V during FRESH and approx. 10 V during RECIRCULATE
L.H.D.
―  Terminal C: approx. 0.5 V during FRESH and approx. 10 V during RECIRCULATE
―  Terminal A: approx. 10 V during FRESH and approx. 0.5 V during RECIRCULATE
Yes
Go to Step 7.
No
Repair the wiring harness between the climate control unit and air intake actuator, then go to Step 9.
4
INSPECT TO SEE WHETHER MALFUNCTION IS IN AIR INTAKE ACTUATOR OR ELSEWHERE
•  Disconnect the air intake actuator connector.
•  Measure the voltages at the following climate control unit terminals.
R.H.D.
―  Terminal 1K (RECIRCULATE motor drive signal)
―  Terminal 1M (FRESH motor drive signal)
L.H.D.
―  Terminal 1M (RECIRCULATE motor drive signal)
―  Terminal 1K (FRESH motor drive signal)
•  Are voltages normal?
Yes
Inspect the air intake actuator, then go to Step 9.
No
Go to the next step.
5
INSPECT TO SEE WHETHER MALFUNCTION IS IN WIRING HARNESS (SHORT TO B+ BETWEEN CLIMATE CONTROL UNIT AND AIR INTAKE ACTUATOR) OR ELSEWHERE
•  Disconnect the climate control unit connector.
•  Measure the voltages at the following climate control unit terminals.
R.H.D.
―  Terminal 1K (RECIRCULATE motor drive signal)
―  Terminal 1M (FRESH motor drive signal)
L.H.D.
―  Terminal 1M (RECIRCULATE motor drive signal)
―  Terminal 1K (FRESH motor drive signal)
•  Are voltages approx. 0 V?
Yes
Go to the next step.
No
Repair the wiring harness between the climate control unit and air intake actuator, then go to Step 9.
6
INSPECT TO SEE WHETHER MALFUNCTION IS IN WIRING HARNESS (SHORT TO GROUND BETWEEN CLIMATE CONTROL UNIT AND AIR INTAKE ACTUATOR) OR ELSEWHERE
•  Turn the ignition switch to the OFF position.
•  Inspect for continuity at the following terminals between the climate control unit and ground.
R.H.D.
―  Terminal 1K (RECIRCULATE motor drive signal)
―  Terminal 1M (FRESH motor drive signal)
L.H.D.
―  Terminal 1M (RECIRCULATE motor drive signal)
―  Terminal 1K (FRESH motor drive signal)
•  Is there continuity?
Yes
Repair the wiring harness between the climate control unit and air intake actuator, then go to Step 9.
No
Go to the next step.
7
INSPECT AIR INTAKE LINK
•  Inspect the air intake links for followings:
―  Is there grease on link?
―  Are the links securely and properly installed?
―  Are the links free of obstructions and hindrances?
•  Are the above items normal?
Yes
Go to the next step.
No
Apply grease to the links. If any the links are damaged, replace the air intake actuator, then go to Step 9.
8
INSPECT TO SEE WHETHER MALFUNCTION IS IN CLIMATE CONTROL UNIT OR AIR INTAKE DOOR
•  Inspect the A/C unit air intake door.
―  Is the door free of obstructions, cracks, and damage?
―  Are the doors securely and properly installed?
•  Are the above items normal?
Yes
Replace the climate control unit, then go to the next step.
No
Remove obstruction, or install the doors in the proper position. If any doors are cracked or damaged, replace them, then go to the next step.
9
VERIFY REPAIR
•  Does the air intake mode change smoothly?
Yes
Troubleshooting completed. Explain repairs to customer.
No
Recheck malfunction symptoms, then repeat from Step 1 if the malfunction recurs.