REFRIGERANT CHARGING
id071000300100
amxzzw00003079
|
Charging Recycled Refrigerant
1. Correctly collect the refrigerant following the instructions for the chlorofluorocarbon (CFC) recovery machine being used.
Adding Compressor Oil
1. Weigh the compressor oil which is exhausted when collecting the refrigerant.
2. When adding refrigerant, add new compressor oil equivalent in weight to the exhausted amount to the refrigerant cycle.
Charging Preparation
1. Close all the valves of the manifold gauge.
amxuuw00003823
|
2. Close all the refrigerant tank valves.
3. Install the manifold gauge set. (See MANIFOLD GAUGE SET CONNECTION.)
4. Connect the vacuum pump hose to the manifold gauge.
5. Connect the tap pin side of the charging hose to the air purge valve of the manifold gauge.
6. Install the refrigerant tank valves to the 4-way joint.
7. Install the 4-way joint to the charging hose (no-tap pin side).
8. Install the refrigerant tanks with the specified amount of refrigerant to the refrigerant tank valves.
9. Connect the vacuum pump hose to the vacuum pump.
10. Perform an evacuation. (See Evacuation.)
Evacuation
1. Open all the valves of the manifold gauge.
amxuuw00003824
|
2. Start the vacuum pump and let it operate for 15 min.
3. Verify that high- and low-pressure side readings of the manifold gauge are at -0.1 MPa {-1 kgf/cm2, -15 psi}.
4. Stop the vacuum pump.
5. Close all the valves of the manifold gauge.
amxuuw00003825
|
6. Wait for 5 min after stopping the vacuum pump, and perform an airtightness check for the refrigerant system. (See Airtightness Check.)
Airtightness Check
1. Verify that the manifold gauge reading has not changed.
amxuuw00003826
|
Charging New Refrigerant
1. Open the refrigerant tank valves.
amxuuw00003827
|
2. Open the high-pressure side valve of the manifold gauge.
amxuuw00003828
|
3. Verify that low-pressure side readings of the manifold gauge is at 0.1 MPa {1 kgf/cm2, 15 psi}.
4. Close the high-pressure side valve of the manifold gauge.
amxuuw00003829
|
5. Inspect for gas leakage from the piping connection using a gas leak detector or a fluorescent agent-detecting UV black light.
6. Inspect for leakage again.
7. Open the high-pressure side valve of the manifold gauge.
amxuuw00003828
|
8. Charge with approx. 1/2 of the specified amount of refrigerant.
9. Close the high-pressure side valve of the manifold gauge.
amxuuw00003829
|
10. Start the engine and actuate the A/C compressor.
11. Open the low-pressure side valve of the manifold gauge.
amxuuw00003830
|
12. Charge the remaining refrigerant (approx. 1/2 of amount of specified refrigerant).
13. Close the low-pressure side valve of the manifold gauge.
amxuuw00003831
|
14. Stop the engine.
15. Perform the leak test. (See Leak Test.)
Leak Test
1. Inspect for gas leakage from the piping connection using a gas leak detector or a fluorescent agent-detecting UV black light.
2. Inspect for leakage again.
3. Disconnect the quick couplers from the charging valves.
amxuuw00003832
|
4. Install the caps to the charging valves.