AIRFLOW MODE ACTUATOR INSPECTION [MANUAL AIR CONDITIONER]


id0740a2801700

Caution
•  If the lever position exceeds the operation range shown in the figure, the circuit in the actuator could be damaged. Always perform an actuator operation inspection with the lever movement within the range shown in the figure.

L.H.D.

1.  Disconnect the negative battery terminal. (See NEGATIVE BATTERY TERMINAL DISCONNECTION/CONNECTION.)

2.  Remove the airflow mode actuator. (See AIRFLOW MODE ACTUATOR REMOVAL/INSTALLATION [MANUAL AIR CONDITIONER].)

3.  Apply battery positive voltage and connect the ground to the airflow mode actuator terminals as indicated in the table below and verify the operation condition.

B+ Terminal

Ground Terminal

Operation

A
B
VENT → DEFROSTER
B
A
DEFROSTER → VENT

amxzzw00004942

4.  Verify that the resistance between terminals D and E, E and F matches the airflow mode actuator operation as shown in the graph.

amxzzw00004943

•  If the operation condition and resistance are not normal, replace the airflow mode actuator. (See AIRFLOW MODE ACTUATOR REMOVAL/INSTALLATION [MANUAL AIR CONDITIONER].)


R.H.D.

1.  Disconnect the negative battery terminal. (See NEGATIVE BATTERY TERMINAL DISCONNECTION/CONNECTION.)

2.  Remove the airflow mode actuator. (See AIRFLOW MODE ACTUATOR REMOVAL/INSTALLATION [MANUAL AIR CONDITIONER].)

3.  Apply battery positive voltage and connect the ground to the airflow mode actuator terminals as indicated in the table below and verify the operation condition.

B+ Terminal

Ground Terminal

Operation

A
B
DEFROSTER → VENT
B
A
VENT → DEFROSTER

amxzzw00004944

4.  Verify that the resistance between terminals D and E, E and F matches the airflow mode actuator operation as shown in the graph.

amxzzw00004945

•  If the operation condition and resistance are not normal, replace the airflow mode actuator. (See AIRFLOW MODE ACTUATOR REMOVAL/INSTALLATION [MANUAL AIR CONDITIONER].)