NO.3 AIR INTAKE MODE DOES NOT CHANGE [MANUAL AIR CONDITIONER]
id0703c2802900
3
|
Air intake mode does not change.
|
DESCRIPTION
|
• Air intake mode does not change when switching REC/FRESH mode.
|
POSSIBLE CAUSE
|
• Air intake actuator malfunction
• Air intake door malfunction
|
Diagnostic procedure
STEP |
INSPECTION |
ACTION |
|
---|---|---|---|
1
|
INSPECT TO SEE WHETHER MALFUNCTION IS IN AIR INTAKE ACTUATOR OR ELSEWHERE
• Disconnect the air intake actuator connector.
• Measure the voltages at the following air intake actuator terminals.
L.H.D.
R.H.D.
• Are voltages normal?
|
Yes
|
Go to the next step.
|
No
|
Go to Step 3.
|
||
2
|
INSPECT AIR INTAKE ACTUATOR
• Inspect air intake actuator.
• Is it normal?
|
Yes
|
Go to the Step 6.
|
No
|
Replace the air intake actuator, then go to Step 8.
|
||
3
|
INSPECT TO SEE WHETHER MALFUNCTION IS IN WIRING HARNESS (SHORT TO B+ BETWEEN CLIMATE CONTROL UNIT AND AIR INTAKE ACTUATOR) OR ELSEWHERE
• Air intake actuator and climate control unit disconnected.
• Measure the voltages at the following air intake actuator terminals.
L.H.D.
R.H.D.
• Are voltages approx. 0 V?
|
Yes
|
Go to the next step.
|
No
|
Repair the wiring harness for short to B+ between the climate control unit and air intake actuator, then go to Step 8.
|
||
4
|
INSPECT TO SEE WHETHER MALFUNCTION IS IN WIRING HARNESS (SHORT TO GROUND BETWEEN CLIMATE CONTROL UNIT AND AIR INTAKE ACTUATOR) OR ELSEWHERE
• Air intake actuator and climate control unit connectors disconnected.
• Switch the ignition to off.
• Inspect for continuity at the following terminals between the air intake actuator and ground.
L.H.D.
R.H.D.
• Is there continuity?
|
Yes
|
Repair the wiring harness for short to ground between the climate control unit and air intake actuator, then go to Step 8.
|
No
|
Go to the next step.
|
||
5
|
INSPECT TO SEE WHETHER MALFUNCTION IS IN WIRING HARNESS (OPEN CIRCUIT BETWEEN CLIMATE CONTROL UNIT AND AIR INTAKE ACTUATOR) OR ELSEWHERE
• Air intake actuator and climate control unit connectors disconnected.
• Switch the ignition to off.
• Inspect for continuity at the following terminals between the climate control unit and air intake actuator.
• Is there continuity?
|
Yes
|
Go to the next step.
|
No
|
Repair the wiring harness for open circuit between the climate control unit and air intake actuator, then go to Step 8.
|
||
6
|
INSPECT AIR INTAKE LINK
• Inspect the air intake links.
• Are the above items normal?
|
Yes
|
Go to the next step.
|
No
|
Apply grease to the links. if any the links are damaged, replace the air intake actuator, then go to Step 8.
|
||
7
|
INSPECT TO SEE WHETHER MALFUNCTION IS IN CLIMATE CONTROL UNIT OR AIR INTAKE DOOR
• Inspect the A/C unit air intake door.
• Are the above items normal?
|
Yes
|
Replace the climate control unit, then go to the next step.
|
No
|
Remove obstruction, or install the doors in the proper position. If any doors are cracked or damaged, replace them, then go to the next step.
|
||
8
|
CONFIRM THAT MALFUNCTION SYMPTOMS DO NOT RECUR AFTER REPAIR
• Does the air intake mode change smoothly?
|
Yes
|
Troubleshooting completed.
Explain repairs to customer.
|
No
|
Recheck malfunction symptoms, then repeat from Step 1 if the malfunction recurs.
|