DTC 21
id070200803300
DTC 21
Airflow mode actuator (potentiometer) (present)
POSSIBLE CAUSE
• Airflow mode actuator malfunction
• Climate control unit malfunction
• Open circuit between airflow mode actuator and climate control unit
• Short circuit between airflow mode actuator (terminal C) and climate control unit (terminal 1W: 24-pin)
Diagnostic Procedure
STEP
INSPECTION
ACTION
1
• Inspect airflow mode actuator.
• Is it okay?
Yes
Go to the next step.
No
Replace airflow mode actuator.
2
• Disconnect air mix actuator connector.
• Is resistance between terminals 1W and 1I of climate control unit connector (24-pin) more than
387 ohms
?
Yes
Go to the next step.
No
Repair wiring harness. (Short circuit)
3
• Disconnect climate control unit connector (24-pin).
• Is resistance between terminals 1B and 1I of climate control unit connector (24-pin) less than
4.8 kilohms
?
Yes
Go to the next step.
No
Repair wiring harness. (Open circuit)
4
• Is resistance between terminals 1B and 1W of climate control unit connector (24-pin) less than
4.2 kilohms
?
Yes
Replace climate control unit.
No
Repair wiring harness. (Open circuit)