STEP
|
INSPECTION
|
ACTION
|
1
|
COOL AIR BLOW OUT INSPECTION
• When both A/C and fan switch in climate control unit are on, does cool air blow out from front vent?
|
Yes
|
Go to next step.
|
No
|
Go to Step 1 of troubleshooting index No.8.
|
2
|
INSPECT CLIMATE CONTROL UNIT POWER SUPPLY FUSE FOR B+ SIGNAL
• Is climate control unit power supply fuse for B+ signal okay?
|
Yes
|
Go to next step.
|
No
|
Inspect for a short to ground on blown fuse circuit.
• Repair or replace as necessary. Install appropriate amperage fuse.
|
3
|
INSPECT AIR INTAKE ACTUATOR
• Inspect air intake actuator.
-
- Is there grease on link?
-
- Is link securely and properly positioned?
-
- Is link free of obstructions?
• Are above items okay?
|
Yes
|
Go to next step.
|
No
|
Apply grease or install link properly and securely, remove obstruction, then go to Step 14.
|
*4
|
INSPECT WIRING HARNESS BETWEEN FUSE BLOCK AND CLIMATE CONTROL UNIT FOR CONTINUITY
• Disconnect climate control unit connector (12-pin).
• Turn ignition switch to ON position.
• Test voltage at climate control unit connector terminal F (B+ signal).
• Is voltage approximately 12 V?
|
Yes
|
Go to next step.
|
No
|
Repair wiring harness between fuse block and climate control unit, then go to Step 14.
|
*5
|
INSPECT WIRING HARNESS BETWEEN CLIMATE CONTROL UNIT AND GROUND FOR VOLTAGE
• Test voltage at climate control unit connector terminal 2L (Ground).
• Is voltage approximately 0V?
|
Yes
|
Go to next step.
|
No
|
Repair wiring harness between climate control unit and ground, then go to Step 14.
|
6
|
VERIFY WHETHER MALFUNCTION IS IN BLOWER UNIT AIR INTAKE DOOR OR ELSEWHERE
• Turn ignition switch to LOCK position.
• Connect climate control unit connector (12-pin).
• Remove air intake actuator.
• Turn ignition switch to ON position.
• Set fan switch to 4th position.
• Does air intake mode (RECIRCULATE, FRESH) change smoothly when air intake link is operated by hand?
|
Yes
|
Go to next step.
|
No
|
Go to Step 12.
|
7
|
INSPECT AIR INTAKE ACTUATOR
• Inspect air intake actuator.
• Is it okay?
|
Yes
|
Go to next step.
|
No
|
Replace air intake actuator, go to Step 14.
|
8
|
INSPECT AIR INTAKE SELECTOR SWITCH AND DEFROSTER SWITCH IN CLIMATE CONTROL UNIT
• Test voltage at climate control unit connector (12-pin) terminals 2K and 2I.
• Is it okay?
|
Yes
|
Go to next step.
|
No
|
Replace climate control unit, then go to Step 14.
|
*9
|
INSPECT WIRING HARNESS BETWEEN CLIMATE CONTROL UNIT AND AIR INTAKE ACTUATOR FOR CONTINUITY
• Turn ignition switch to LOCK position.
• Is there continuity between following climate control unit connector (12-pin) terminal and air intake actuator connector terminal?
-
- Terminal D -Terminal 2K (FRESH signal)
-
- Terminal F -Terminal 2I (RECIRCULATE signal)
|
Yes
|
Go to next step.
|
No
|
Repair wiring harness between climate control unit and air intake actuator, then go to Step 14.
|
*10
|
INSPECT WIRING HARNESS BETWEEN CLIMATE CONTROL UNIT AND AIR INTAKE ACTUATOR FOR SHORT TO GROUND
• Is there continuity between following climate control unit connector (12-pin) terminal and ground?
-
- Terminal 2K (FRESH signal)
-
- Terminal 2I (RECIRCULATE signal)
|
Yes
|
Repair wiring harness between climate control unit and air intake actuator, then go to Step 14.
|
No
|
Go to next step.
|
*11
|
INSPECT WIRING HARNESS BETWEEN CLIMATE CONTROL UNIT AND AIR INTAKE ACTUATOR FOR SHORT TO B+
• Turn ignition switch to ON position
• Test voltage at following climate control unit connector (12-pin) terminal.
-
- Terminal 2K (FRESH signal)
-
- Terminal 2I (RECIRCULATE signal)
• Is voltage approximately 12 V?
|
Yes
|
Repair wiring harness between climate control unit and air intake actuator, then go to Step 14.
|
No
|
Replace climate control unit, then go to Step 14.
|
12
|
INSPECT BLOWER UNIT AIR INTAKE DOOR
• Is there any foreign material or obstruction in blower unit air intake door?
|
Yes
|
Remove obstruction, then go to Step 14.
|
No
|
Go to next step.
|
13
|
VERIFY THAT BLOWER UNIT AIR INTAKE DOOR IS POSITIONED SECURELY AND PROPERLY
• Is blower unit air intake door securely and properly positioned?
|
Yes
|
Inspect air intake door for cracks or damage, then go to next step.
|
No
|
Install air intake door securely in proper position, then go to next step.
|
14
|
VERIFY THAT MALFUNCTION SYMPTOMS DO NOT RECUR AFTER REPAIR
• Does malfunction disappear?
|
Yes
|
Troubleshooting completed.
Explain repairs to customer.
|
No
|
Recheck malfunction symptoms, then repeat from Step 1 if malfunction recurs.
|