DTC S2.1


id070200811100

DTC S2.1

Air mix actuator (motor lock)

POSSIBLE CAUSE
•  Air mix actuator malfunction
•  Heater unit (air mix link and/or air mix crank) malfunction
•  Climate control unit malfunction
•  Open or short circuit between air mix actuator and climate control unit

Diagnostic Procedure

STEP

INSPECTION

ACTION

1
•  Disconnect air mix actuator connector.
•  Connect battery positive voltage to terminal A (or terminal F) and ground to terminal F (or terminal A) of air mix actuator connector.
•  Does air mix actuator operate?
Yes
Connect air mix actuator connector, then go to Step 3.
No
Go to the next step.
2
•  Remove air mix actuator.
•  Operate air mix link by hand.
•  Does air mix link operate smoothly?
Yes
Replace air mix actuator. (See AIR MIX ACTUATOR REMOVAL/INSTALLATION.)
No
Replace air mix link and/or air mix crank.
3
•  Disconnect climate control unit connector.
•  Connect battery positive voltage to terminal K (or terminal L) and ground to terminal L (or terminal K) of climate control unit connector.
•  Does air mix actuator operate?
Yes
Replace climate control unit. (See CLIMATE CONTROL UNIT REMOVAL/INSTALLATION.)
No
Repair wiring harness.