Cooldown Test Too Cold to Start
Test 1 - 2:
Test 3 - 6:
Test 7:
SYMPTOM
COOLDOWN TEST TOO COLD TO START
WHEN MONITORED
When executing the Cooldown Test.
SET CONDITION
This message will be displayed if the A/C - Heater Control Module sees evaporator temperature below 12.7 degrees C (55 degrees F) when executing the Cooldown Test.
POSSIBLE CAUSES
- Evaporator temperature too low
- Check for HVAC DTCs
- Check for PCM DTCs
- Evaporator temperature sensor
- Sensor ground circuit high resistance
- Evaporator temperature sensor signal circuit high resistance
- A/C-Heater control module