Compressor HVAC: Testing and Inspection
Climate Control System
Component Tests
A/C Compressor - External Leak Test
1. Install the appropriate adapter from the Pressure Test Kit on the port of the A/C compressor, using the existing manifold retaining bolt.
2. Connect the high and low-pressure lines of a manifold gauge set or a refrigerant recovery/recycling station to the corresponding fittings on the A/C Flush Adapter Kit.
3. Attach the center hose of a manifold gauge set to a refrigerant container standing in an upright position.
4. Hand-rotate the compressor shaft 10 complete revolutions to distribute the oil inside the A/C compressor.
5. Open the low-pressure gauge valve, the high-pressure gauge valve and the valve on the refrigerant container to allow the refrigerant vapor to flow into the A/C compressor.
6. Using the Refrigerant Leak Detector, check for leaks at the compressor shaft.
7. If a shaft seal leak is found, install a new compressor shaft seal. If an external leak is found, install a new A/C compressor.
8. When the leak test is complete, recover the refrigerant from the compressor.