REFRIGERANT CHARGING
id071000700400
a30zzw00002754
|
Refrigerant type |
Specified refrigerant amount (reference) |
---|---|
HFO-1234yf (R-1234yf)
|
1,185—1,235 g {41.80—43.56 oz}
|
Refrigerant (HFO-1234yf) recovery
1. Switch the main power OFF and wait for 100 s or more.
2. Correctly collect the refrigerant following the instructions for the chlorofluorocarbon (CFC) recovery machine being used.
Adding compressor oil
1. When collecting the refrigerant, weigh the exhausted compressor oil.
2. When adding refrigerant, add new compressor oil to the refrigeration cycle equivalent in weight to the exhausted amount.
Preparation for charging
1. Close all the valves of the manifold gauge.
a30zzw00002755
|
2. Close the refrigerant tank valve.
3. Install the manifold gauge set. (See MANIFOLD GAUGE SET CONNECTION.)
4. Attach the vacuum pump hose to the manifold gauge.
5. Attach the charging hose (tap pin side) to the air purge valve of the manifold gauge.
6. Attach the charging hose (no-tap pin side) to the refrigerant tank.
7. Place the refrigerant tank on the scale.
8. Attach the vacuum pump hose to the vacuum pump.
9. Perform vacuum discharging. (See Vacuum discharging.)
Vacuum discharging
1. Switch the main power OFF and wait for 100 s or more.
2. Open all valves of the manifold gauge.
a30zzw00002756
|
3. Start the vacuum pump and perform vacuum discharging on the refrigeration cycle for 15 min.
4. Verify that high- and low-pressure side readings of the manifold gauge are at -0.1 MPa {-1 kgf/cm2, -15 psi}.
5. Stop the vacuum pump.
6. Close all the valves of the manifold gauge.
a30zzw00002757
|
7. Wait for 5 min after stopping the vacuum pump, and perform an airtightness check for the refrigerant system. (See Air tightness check.)
Air tightness check
1. Verify that the manifold gauge reading has not changed.
a30zzw00002758
|
Refrigerant (HFO-1234yf) charging
1. Open the refrigerant tank.
a30zzw00002759
|
2. Measure the weight of the refrigerant tank.
3. Open the low pressure valve of the manifold gauge.
a30zzw00002760
|
4. Verify that low-pressure side readings of the manifold gauge is at 0.1 MPa {1 kgf/cm2, 15 psi}.
5. Close the low pressure side valve of the manifold gauge.
a30zzw00002761
|
6. Inspect for gas leakage from the piping connection using a gas leak detector or a fluorescent agent-detecting UV black light.
7. Inspect again for gas leakage from the piping connection using a gas leak detector or a fluorescent agent-detecting UV black light.
8. Open the low pressure valve of the manifold gauge.
a30zzw00002760
|
9. Charge with refrigerant until the weight of refrigerant tank has decreased 600 g {21.2 oz} from the amount in Step 2.
10. Close the low pressure side valve of the manifold gauge.
a30zzw00002761
|
11. Switch the main power ON (READY ON) and activate the electric compressor.
12. Open the low pressure side valve of the manifold gauge and inject refrigerant until the weight of the refrigerant tank decreases from the amount in Step 2 to the normal amount.
a30zzw00002760
|
13. Close the low pressure side valve of the manifold gauge.
a30zzw00002761
|
14. Switch the main power OFF.
15. Perform the leak test. (See Leak test.)
Leak test
1. Inspect for gas leakage from the piping connection using a gas leak detector or a fluorescent agent-detecting UV black light.
2. Inspect for gas leakage from the piping connection using a gas leak detector or a fluorescent agent-detecting UV black light.
3. Remove the quick coupler from the charging valve located on the high and low pressure lines.
a30zzw00002762
|
4. Attach the cap to the charging valve.