Refrigerant: Testing and Inspection




REFRIGERANT IDENTIFICATION TESTING

1. Follow the instructions included with the Refrigerant Identifier with Air-Radiator to obtain the sample for testing.

NOTE:A Refrigerant Blend Identifier with Printer must be used to identify gas samples taken directly from the refrigeration system or storage containers prior to recovering or charging the refrigerant system. Follow the instructions included with the Refrigerant Blend Identifier with Printer to obtain the sample for testing.
2. The Refrigerant Blend Identifier with Printer will display one of the following:

- If the purity level of R-134a is 98% or greater by weight, the green PASS light emitting diode (LED) will light. The weight concentrations of R-134a, R-12, R-22, hydrocarbons and air will be displayed on the digital display.
- If the refrigerant R-134a does not meet the 98% purity level, the red FAIL LED will light and an alarm will sound alerting the user of potential hazards. The weight concentrations of R-134a, R-12, R-22 and hydrocarbons will be displayed on the digital display.
- If the hydrocarbon concentrations are 2% or greater by weight, the red FAIL LED will light, "Hydrocarbon High" be displayed on the digital display, and an alarm will sound alerting the user of potential hazards. The weight concentrations of R-134a, R-12, R-22 and hydrocarbons will also be displayed on the digital display.

3. The percentage of air contained in the sample will be displayed if the R-134a content is 98% or greater. The Refrigerant Blend Identifier with Printer eliminates the effect of air when determining the refrigerant sample content because air is not considered a contaminant, although air can affect A/C system performance. When the Refrigerant Blend Identifier with Printer has determined that a refrigerant source is pure (R-134a is 98% or greater by weight) and the air concentration levels are 2% or greater by weight, the scan tool will prompt the user if an air purge is desired.

4. If contaminated refrigerant is detected, repeat the refrigerant identification test to verify that the refrigerant is indeed contaminated.