HIGH VOLTAGE BATTERY DOES NOT COOL
id300300000900
Outline
Malfunction symptom |
High voltage battery does not cool |
---|---|
Description
|
• It takes a long time to fully charge with quick charge.
• Frequency of poor acceleration or insufficient power is high.
|
Possible cause
|
High voltage battery cooling system operation malfunction:
• Refrigerant leakage
• Electric compressor malfunction
• Electric expansion valve (in high voltage battery) malfunction
• 2way valve for refrigerant malfunction
• 3way valve for refrigerant malfunction
• Refrigerant passage blockage
• Condenser fin blockage/separation
• Cooling fan malfunction
• Ambient temperature sensor malfunction
• Refrigerant pressure sensor No.2 malfunction
• Temperature sensor of refrigerant line for evaporator outlet malfunction
• Temperature sensor of air for PTC/temperature sensor of refrigerant line for electric compressor outlet malfunction
• Temperature sensor of refrigerant line for condenser outlet malfunction
• Temperature sensor of refrigerant line for the high voltage battery malfunction
• Poor contact of cooling plate with battery module
High voltage battery malfunction:
• Battery cell malfunction (deterioration)
• High voltage battery module temperature sensor malfunction
|
System wiring diagram
|
• Not applicable
|
Connector diagram
|
• Not applicable
|
Diagnostic Procedure
Step |
Inspection |
Results |
Action |
---|---|---|---|
1
|
VERIFY HIGH VOLTAGE BATTERY COOLING RELATED DTCs
• Perform the DTC inspections for the following modules.
(See DTC INSPECTION.)
• Is a DTC displayed?
|
Yes
|
Repair the malfunctioning location according to the applicable DTC troubleshooting.
(See DTC TABLE [PCM (e-SKYACTIV)].)
|
No
|
Go to the next step.
|
||
2
|
INSPECT REFRIGERANT PRESSURE
• Inspect the refrigerant pressure.
(See REFRIGERANT PRESSURE CHECK.)
• Is the refrigerant pressure normal?
|
Yes
|
Go to the next step.
|
No
|
Inspect the refrigerant system following the symptom troubleshooting procedure.
|
||
3
|
VERIFY COOLING PERFORMANCE OF HIGH VOLTAGE BATTERY COOLING SYSTEM
• Connect the M-MDS to the DLC-2.
• Display BECM PID [HV_BATT_OUT_REFR_TEMP] using the M-MDS.
(See PID/DATA MONITOR INSPECTION.)
• Record the PID [HV_BATT_OUT_REFR_TEMP] value.
• Select the following menu and perform [Cooling for drive battery] for [Compulsory operating Air Conditioner] for 10 min.
• Verify the BECM PID [HV_BATT_OUT_REFR_TEMP] value.
• Is the monitor value 5 °C {41 °F} or more lower than before the climate control system forced operation?
|
Yes
|
Complete the symptom troubleshooting.
Return to the diagnostic procedure of other symptom troubleshooting.
|
No
|
Go to the next step.
|
||
4
|
VERIFY IF HIGH VOLTAGE BATTERY TEMPERATURE IS AT TEMPERATURE WHERE OPERATION VERIFICATION OF ELECTRIC EXPANSION VALVE (IN HIGH VOLTAGE BATTERY) IS POSSIBLE
• Connect the M-MDS to the DLC-2.
• Display BECM PID [HV_BATT_TEMP_MAX] using the M-MDS.
(See PID/DATA MONITOR INSPECTION.)
• Verify the BECM PID [HV_BATT_TEMP_MAX] value.
• Is the monitor value 40 °C {104 °F} or more?
|
Yes
|
Refer to Step 3 and perform the [Cooling for drive battery] in the [Compulsory operating Air Conditioner] for 5 min until the PID [HV_BATT_TEMP_MAX] value is less than 5 °C {41 °F}.
|
No
|
Go to the next step.
|
||
5
|
VERIFY ELECTRIC EXPANSION VALVE (IN HIGH VOLTAGE BATTERY) OPERATION
• Connect the M-MDS to the DLC-2.
• Select the following menu and perform the [Expansion valve for cooling battery] for [Self-Diagnosis Air Conditioner control valves].
• Select the following menu and perform the air conditioner control valve on-board diagnosis.
• Is the troubleshooting result normal?
|
Yes
|
Perform the climate control system refrigerant system performance test.
|
No
|
Replace the high voltage battery.
|