ELECTRIC COMPRESSOR DOES NOT OPERATE EVEN WITH MAX COLD SETTING [FULL-AUTO AIR CONDITIONER]
id0703c1702100
Malfunction symptom |
Electric compressor does not operate even with MAX COLD setting |
|
---|---|---|
Details
|
• Electric compressor does not operate even if airflow temperature setting is MAX COLD
|
|
Possible Cause
|
• Active air shutter malfunction
• Cooling fan operation malfunction
• A/C pressure sensor (motor room side) malfunction
• A/C pressure sensor (high voltage battery side) malfunction
• Evaporator temperature sensor malfunction
• Ambient temperature sensor malfunction
• Malfunction of temperature sensor of refrigerant line for condenser outlet
• Condenser malfunction
• Electric compressor malfunction
|
Diagnostic Procedure
Step |
Inspection |
Action |
|
---|---|---|---|
1
|
INSPECT REFRIGERANT PRESSURE
• Inspect the refrigerant pressure.
(See REFRIGERANT PRESSURE CHECK.)
• Is the pressure less than 0.2 on the high and low pressure sides?
|
Yes
|
Go to the next step.
|
No
|
Go to Step 3.
|
||
2
|
INSPECT SYSTEM PIPING
• Verify if there is gas leakage from the system piping using the gas leak tester.
(See REFRIGERANT CHARGING.)
• Is the system piping normal?
|
Yes
|
Replace the high voltage battery and perform the repair completion verification.
|
No
|
Replace the O-ring of the malfunctioning location (system piping connecting area). Or replace the malfunctioning location of the system piping and perform the repair completion verification.
|
||
3
|
INSPECT ACTIVE AIR SHUTTER
• Inspect the active air shutter.
• Is the active air shutter normal?
|
Yes
|
Go to the next step.
|
No
|
Repair or replace the malfunctioning location and perform the repair completion verification.
|
||
4
|
INSPECT COOLING FAN OPERATION
• Inspect the cooling fan control.
(See COOLING FAN MOTOR INSPECTION.)
• Is the cooling fan operation normal?
|
Yes
|
Go to the next step.
|
No
|
Repair or replace the malfunctioning location and perform the repair completion verification.
|
||
5
|
INSPECT REFRIGERANT PRESSURE SENSOR (MOTOR ROOM SIDE)
• Inspect the refrigerant pressure sensor (motor room side).
• Is the refrigerant pressure sensor normal?
|
Yes
|
Go to the next step.
|
No
|
Repair or replace the malfunctioning location and perform the repair completion verification.
|
||
6
|
INSPECT REFRIGERANT PRESSURE SENSOR (HV BATTERY SIDE)
• Inspect the refrigerant pressure sensor (high voltage battery side).
• Is the refrigerant pressure sensor normal?
|
Yes
|
Go to the next step.
|
No
|
Repair or replace the malfunctioning location and perform the repair completion verification.
|
||
7
|
INSPECT EVAPORATOR TEMPERATURE SENSOR
• Inspect the evaporator temperature sensor.
• Is the evaporator temperature sensor normal?
|
Yes
|
Verify the evaporator temperature installation condition and repair the installation position.
Go to the next step.
|
No
|
Repair or replace the malfunctioning location and perform the repair completion verification.
|
||
8
|
INSPECT AMBIENT TEMPERATURE SENSOR
• Inspect the ambient temperature sensor.
• Is the ambient temperature sensor normal?
|
Yes
|
Go to the next step.
|
No
|
Repair or replace the malfunctioning location and perform the repair completion verification.
|
||
9
|
INSPECT TEMPERATURE SENSOR OF REFRIGERANT LINE FOR CONDENSER OUTLET
• Inspect the temperature sensor of refrigerant line for condenser outlet.
• Is the temperature sensor of refrigerant line for condenser outlet normal?
|
Yes
|
Go to the next step.
|
No
|
Replace the temperature sensor of refrigerant line for condenser outlet and perform the repair completion verification.
|
||
10
|
INSPECT CONDENSER
• Inspect the condenser.
(See CONDENSER INSPECTION.)
• Is there cool airflow?
|
Yes
|
Go to the next step.
|
No
|
Replace the condenser and perform the repair completion verification.
|
||
11
|
INSPECT CONDENSER FOR HIGH TEMPERATURE MALFUNCTION
• Open the hood and facilitate heat radiation by blowing air using a fan.
• Verify if operation starts after 30 min.
|
Yes
|
Explain to the customer that it is a temporary fail-safe measure.
|
No
|
Replace the electric compressor and perform the repair completion verification.
|
||
Repair completion verification
|
VERIFY THAT MALFUNCTION DOES NOT RECUR AFTER REPAIRS
• Verify that the electric compressor operates normally.
|
Yes
|
Troubleshooting completed (explain repair contents to customer).
|
No
|
Refer to the controller area network (CAN) malfunction diagnosis flow to inspect for a CAN communication error.
If the CAN communication is normal, perform the diagnosis from Step 1.
|